Abstract

ABSTRACTThis paper describes the power quality analysis applied on 6 kW building-integrated photovoltaic system (BIPVS) and its economic study. A monitoring system was implemented using virtual instrumentation to measure irradiance, ambient temperature and electric variables of the photovoltaic (PV) system. The study includes a period of one year from September 2015 to August 2016 and for this the IEEE 929-2000 standard guidelines were followed. The results indicate that the power quality parameters: % THDv, frequency, nominal voltage and flicker meet the standard limits mentioned. Economic analysis of the PV system using the RETScreen™ software is also presented. The results show a net present value of USD 35,157 for a period of 20 years with an annual energy saving of USD 1750. Greenhouse gas emissions avoided by the use of solar energy are 6.6 t CO2 per year.