Abstract

MMC-HVDC has the characteristics of limited amplitude, controlled phase angle and unequal positive and negative sequence impedance. Therefore, the fault characteristics of flexible direct system and AC power grid tie line are quite different from traditional synchronous power supply, which may affect the performance of AC power grid sudden variable protection. Therefore, a new AC protection method based on positive sequence current sudden variable impedance is proposed. The results show that when an in zone fault occurs, the direction of current sudden changes at both ends is the same, and the positive sequence impedance may approach the line impedance; When an out of area fault occurs, the current abrupt variables at both ends have opposite directions and equal sizes, and the positive sequence impedance is much greater than the line impedance. Based on the above characteristics, the criteria of fault start up and fault type are constructed. The simulation results show that the protection method can realize fault discrimination quickly and reliably.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.