Abstract

An approach to detect the secondary arc extinction is proposed here for single-phase auto-reclosing of non-compensated transmission lines. It consists on the analysis of the line side voltage phasors in the modal domain to safely and rapidly identify the presence and the extinction of secondary arc in the line. The procedure can also determine the arc re-ignition if it occurs during the line dead time. Since the proposed approach requires only the voltage phasors at one line terminal, it can be easily implemented in existing Intelligent Electronic Devices (IEDs) with no additional hardware or equipment requirement. Data from the Brazilian Power Grid were used to generate the case studies through the Electromagnetic Transients Program (EMTP). Moreover, field recordings were used to validate the proposed approach. A qualitative comparison with existing methods was accomplished and the obtained results reveal the proposed scheme efficiency, reliability and robustness.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.