Abstract
When secondary arc is caused by single phase tripping, arc should be extinguished prior to high speed reclosing which can make the system restore. In this paper, we analyzes secondary arc extinction by applying two methods that are shunt reactor and High Speed Grounding Switches (HSGS). To verify the effects of these methods in arc extinction aspects, two factors are discussed. One is secondary arc extinction time, and another is recovery voltage. Especially, secondary arc waveform and amplitude value are analyzed to identify the effects of arc extinction methods. Simulation is conducted by using ElectroMagnetic Transient Program (EMTP) based on actual Korea 765kV transmission system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of International Council on Electrical Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.