Abstract
A series of tests was conducted to unlock the potential application of MgO/water-EG (ethylene glycol) nanofluids (NF) in a double-pipe heat exchanger (HEX). The overall heat transfer coefficient (HTC), the inlet temperature of the working fluid, the fluid pressure drop (FPD), friction factor (FF) and the hydraulic performance index of the NF within the HEX were experimentally measured. Fouling of nanoparticles (NPs) within the Hex was also studied and modelled using asymptotic particulate fouling model. Results showed that MgO NPs can enhance the HTC by 39% at Re=10,500 and wt.% = 0.3 in the turbulent regime. Also, the presence of MgO NPs augmented the FF and the FPD values. The former was enhanced 33.8%, while the latter was augmented by 37% both at wt.% = 0.3 and at Reynolds number = 10,500. Results also revealed that the formation of porous particulate fouling layer on the internal wall of the inner tube creates a fouling thermal resistance which changes asymptotically with time. Overall, MgO/water-ethylene glycol shows a great potential to be used as a coolant within a HEX.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.