Abstract
Comprehensive standard tests were conducted on 33 kV line-post porcelain insulators in order to improve their performance in harsh environment in comparison to the newly introduced polymeric ones. These tests are the lightning impulse withstand and flashover tests, and the AC artificial pollution tests. The latter were conducted in a salt-fog chamber. Silicone rubber insulators showed superior performance than adding heat-shrinkable and wraparound creepage extenders to the existing line-post porcelain insulators or using new polymeric insulators.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.