Abstract

Electrical insulators of the Provincial Electricity Authority (PEA) of medium system are mostly porcelain insulator types that consists of suspension, pin type, line post, and pin post insulators. The distribution lines will be polluted by industrial contaminants, salt fog or natural dust. Experience shows that pollution flashover is one of the main natural calamities harming and affecting the voltage stability and reliability of distribution system. This paper compares the test results obtained from artificial pollution tests according to IEC 60507 with line post type and pin post type insulators of medium system under same test conditions. The salt fog test results indicate that the pollution flashover performance of line post insulator is less than to 50 percent of wet power frequency withstand voltage at equivalent salt deposit density (ESDD) = 0.5 mg/cm <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sup> and the leakage current (LC) of line post insulator increased to 10.2 mA at ESDD = 0.5 mg/cm <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sup> at nominal voltage. In the experiment indicate that AC pollution flashover performance of pin post insulator has better than line post insulator in the serious pollution area.