Abstract

In this paper, turbulent thermo-hydraulic analysis of water-to-water passively augmented DPHX with helical baffles is studied by varying the parameters, mass flow rate and baffle spacing. The baffles in annulus side of the inner pipe augments the rate of heat transfer on comparing with the simple DPHX. The influence of spacing between baffles on the heat transfer rate is investigated by varying the governing parameters. The Reynolds number is varied between 22,000 and 12, 5000 for three different baffle spacing (β) values of 75 mm, 100 mm and 125 mm. The thermo-hydraulic performance parameters pressure drop, Nusselt number and friction factor are examined and put forth corresponding to experimental data. From the results, it is inferred that the effect of baffles on the annulus side of the hot fluid flows through the inner pipe enhances heat transfer rate with increase in the Nu and decreases as the baffle spacing increases.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.