Abstract

This study explores the impact of wavy corrugated twisted tape inserts on enhancing heat transfer and reducing pressure drop in a double pipe heat exchanger. Cu inserts with twist ratios of 3.2, 4.2, and 5.2 were used to create turbulence in the inner tube. Varying water flow rates and measuring bulk mean temperatures at different points revealed significant improvements in heat transfer over smooth tubes. The insert with a 3.2 twist ratio achieved the highest Nusselt number increase (185%) and a 36.33% rise in the friction factor. These results highlight the effectiveness of wavy corrugated twisted tape inserts for optimizing heat transfer, with a 3.2 twist ratio identified as the most effective. Across Reynolds numbers from 4000 to 18000, Nusselt number increases were 77.75% for a 5.2 twist ratio, 167% for a 4.2 twist ratio, and 185% for a 3.2 twist ratio. Friction factors rose by approximately 10.42% for a 5.2 twist ratio, 32.54% for a 4.2 twist ratio, and 36.33% for a 3.2 twist ratio, demonstrating the relationship between twist ratio, heat transfer enhancement.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.