Abstract

This work addresses Experimental investigations of heat transfer and friction factor characteristics in a concentric double pipe heat exchanger (square duct inner and circular tube outer) using full length twisted tapes of different twist ratios. The data were taken for Reynolds number well in the laminar region (Re =30-1100) with twisted tapes of twist ratios (y=2.66 and y=3.55). Experiments were carried out for constant wall temperature boundary condition using Ethylene glycol as working fluid; the results demonstrate that as twist ratio decreases, the twisted tape gives better heat transfer enhancement. Isothermal friction factors were found to be 6 to13 times the plain duct values. Mean Nusselt number for the twisted tapes are higher than those for the plain duct around 6.0 and 5.30 times for y=2.55 and y=3.66 respectively. The experimental result shows that Nusselt numbers are found to be 5.44 -7.49 and 2.46- 4.88 times the plain square duct forced convection values based on constant flow rate and constant pumping power criteria respectively, for y =2.66.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.