Abstract

Power system comprises of various over voltages which are transient in nature namely lightning and switching phenomenon under abnormal conditions which cause flashover in Gas Insulated Bus-duct (GIB) if not protected properly. So, there is a necessity for GIS to have withstanding capability of lightning and switching. Otherwise they may cause shut down of the system. In this work, 1050 kV Lightning Impulse and 750 kV Switching Impulse is superimposed on normal frequency voltage class of 100 kV, 132 kV and 145kV and are given to 1-ΦGIB for finding peak radial movement for Al and Cu particles. The movement patterns for both lightning and switching over voltages are compared. All the simulation results are shown in this paper.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.