Abstract

This paper employs a hybrid model of a power transformer winding for accurate partial discharge (PD) location. The hybrid model greatly reduces the computation complexity of the multi-conductor transmission line (MTL) model, yet retains the ability to accurately represent a winding. Having obtained the transfer functions of the hybrid model, PD signals can be calculated from both line-end and neutral-end at a set of detecting points. Subsequently, the pairs of the calculated signals are compared and a PD is located at the point where the minimum normalized Euclidean distance or F-ratio of the two signals is detected. In order to enhance computation efficiency a two-round technique, which includes a coarse round and a precise round, is developed and a guideline for section division is given. The influence of noise introduced by measurement devices has also been considered. To reduce the noise meanwhile preserve the feature waveforms, an adaptive morphological filter is employed. Simulation studies have shown that it is accurate and feasible to perform PD location using the hybrid model even with the presence of Gaussian noise.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.