Abstract

Multi-conductor transmission line model (MTLM) of transformer winding has been used to find partial discharge (PD) location in transformers. To decrease computational complexity of the model, two methods for calculation of model parameters were studied and the most suitable method was chosen based on comparison between measured and calculated transfer functions of a 132 kV/20 kV transformer. To investigate the accuracy of MTLM in PD localization, PD pulses produced by a PD calibrator were injected into different points of a research 20 kV/0.4 kV transformer and measured at both ends of the winding. The sectional winding transfer functions computed by the model were used to refer measured PD signals to possible PD locations. Then by comparison of referred signals, PD location in the winding was estimated.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.