Abstract

In this paper, the effect of parameters of solar absorption system such as evaporator, absorber, condenser, generator temperatures and the mass of the solution on the evaporator cooling load and the coefficient of performance has been explained theoretically. The results show that, increasing of evaporator and condenser temperatures increase the evaporator cooling load, performance coefficient and the Ratio of Circulation while increasing the temperature of condenser and absorber decreases the evaporator cooling load, performance coefficient and the Circulation Ratio. In addition, increasing the solution mass increases the refrigeration power while the performance coefficient and the Circulation Ratio was constant at increasing the solution mass. The reached maximum cooling load was (1.932 kW) at 15 kg solution mass and 100 °C generator temperature, the maximum COP was 0.774 at (10 °C) temperature of evaporator and the peak Circulation Ratio was 0.3066 at (30 °C) temperature of absorber and (100 °C) temperature of generator.