Abstract

AbstractTo reduce energy consumption, the earth‐to‐air heat exchanger (EAHE) is a suitable technique for cooling and heating buildings. This paper studies numerically the effect of some design parameters (pipe diameter, inlet condition, pipe length, and outlet condition) on the overall performance of the EAHE system. Four diameters of the EAHE pipe (2, 3, 4, and 6 in) are studied and this numerical study has been done for summer and winter seasons for Nasiriyah city in southern Iraq. First, the built numerical model was validated against the experimental model, and the results of comparison showed a good consensus. After the validation and by using computational fluid dynamics modeling, the overall performance of the EAHE system with all pipe diameters was analyzed with ranges of air velocity, DBT or inlet temperature, and a pipe length of 50 m. The simulated results showed that the EAHE system with 6 in pipe diameter has the best values of overall performance, but from the thermal performance point of view, the 2 in pipe diameter is more suitable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.