Abstract

In this paper, the Fourier-based synchrosqueezing transform (FSST) method is introduced into the power system to realize low frequency oscillation identification. Firstly, the modal components of low frequency oscillation signal are separated by FSST, and calculating the instantaneous parameters including magnitude, frequency and phase of every mode component with Hilbert transform. Then, calculating the damping ration of every modal component based on above parameters and derived the formulas. Thus, it realized effective identification of modal parameters of low frequency oscillation signal. The experimental results of simulated data and 16-generator system demonstrate the validity and correctness of the FSST method. Comparing with the classical Prony method shows that the FSST method is better in the identification accuracy when the low frequency oscillation signal is polluted by noise. Finally, the effectiveness of the FSST in Actual power grid is verified based on the real data from Sichuan power grid.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.