In this paper, an overload and short-circuit protection method is proposed for voltage source inverter-based uninterruptible power supply (UPS) system. In order to achieve high reliability and availability of the UPS, short circuit and overload protection scheme are necessary. When overload or short circuit happens, using the proposed control method, the amplitude of the output current can be limited to a constant value, which can be set by the customer to avoid the destruction of the power converter, and to obtain a faster recovery performance as well. The detailed principle of the proposed protection method is discussed in this paper. It mainly contains three parts in the control diagram for current limit, first is the anti-windup in the voltage and current controllers, then the feedforward of the capacitor voltage to the current control loop, the last is the fast reset of the resonant part of the current controller when overcurrent happens. The procedure of developing the control method is also presented in the paper. Experimental results on a commercial UPS system are presented to verify the effectiveness of the control method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.