Abstract

This paper presents two add-on features for the voltage control scheme of directly voltage-controlled distributed energy resource units (VC-DERs) of an islanded microgrid to provide overcurrent and overload protection. The overcurrent protection scheme detects the fault, limits the output current magnitude of the DER unit, and restores the microgrid to its normal operating conditions subsequent to fault clearance. The overload protection scheme limits the output power of the VC-DER unit. Off-line digital time-domain simulation studies, in the EMTDC/PSCAD software environment, demonstrate the feasibility and desirable performance of the proposed features. Real-time case studies based on an RTDS system verifies performance of the hardware-implemented overload and overcurrent protection schemes in a hardware-in-the-loop environment.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.