Abstract

In order to develop high efficiency fire floating pump, 250YYB-250 fire floating pump was taken as an example. The orthogonal experiment of L9 (34), which contains factors with three levels of blade numbers of impeller, outlet angle, impeller fold-angle, was performed to design nine types of impellers. Numerical simulation of whole flow field based on Fluent was adopted to perform an orthogonal test, the order of geometric parameters affects the performance of fire floating pump with complex impeller. The best design scheme for pump model was acquired. Meanwhile, the optimized design scheme was determined, and corresponding test was carried out. It demonstrated that the efficiency of the final optimal design model pump at rated flow point is of 85%. The efficiency is higher than the national standards, which verified the feasibility of the method of orthogonal design in pump design.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.