Abstract

The most significant development in car park ventilation design has been the introduction of Impulse Ventilation. It is an innovative alternative to traditional systems and provides a number of significant benefits. The ventilation of car parks is essential for removing vehicle exhausts Fumes and smoke in case of fire containing harmful pollutants. So design of impulse systems is usually proven by use of CFD (Computational Fluid Dynamic) analysis. In this study considered one of the car parking basement which is in Riyadh, Saudi Arabia and study was conducted by using ANSYS-Fluent. The field study was carried to collect the actual data of boundary conditions for CFD simulation. In this study, two Cases of jet fan smoke ventilation systems were considered, one has 8 jet fans according to the customer and another one has 11 jet fans which positions were changed accordingly. Base on the comparison of simulation data, ventilation system with 11 jet fans can help to improve the evacuation of fumes in the car parking area and it is also observed that the concentration of CO minimized within 15 minutes.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.