Abstract
Different methods are developed for mitigation of ferro-resonance in high-voltage gas insulated substations (GISs). The main components, which have impacts on probability of occurrence of ferro-resonance, are grading capacitance of circuit breakers (CBs) and internal loss of potential transformers (PTs). However, by using active or passive damping resistance in the secondary of PTs, the probability of occurrence of ferro-resonance can be decreased substantially. It is worth mentioning that the thermal limitations of PTs restrict us to dissipate a lot of energy in the damping resistance. Therefore, in this paper, both thermal and electrical aspects of ferro-resonance are considered and modeled to obtain the optimum value of damping resistance for mitigation of ferro-resonance. The proposed model to find the optimum value is based on robust optimization programming. The proposed model is tested and validated on two GISs in Iran.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Journal of Electrical Power & Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.