Abstract

AbstractTo ensure the electrical power supply, inspections are frequently performed in the power grid. Nowadays, several inspections are conducted considering the use of aerial images since the grids might be in places that are difficult to access. The classification of the insulators' conditions recorded in inspections through computer vision is challenging, as object identification methods can have low performance because they are typically pre‐trained for a generalized task. Here, a hybrid method called YOLOu‐Quasi‐ProtoPNet is proposed for the detection and classification of failed insulators. This model is trained from scratch, using a personalized ultra‐large version of YOLOv5 for insulator detection and the optimized Quasi‐ProtoPNet model for classification. For the optimization of the Quasi‐ProtoPNet structure, the backbones VGG‐16, VGG‐19, ResNet‐34, ResNet‐152, DenseNet‐121, and DenseNet‐161 are evaluated. The F1‐score of 0.95165 was achieved using the proposed approach (based on DenseNet‐161) which outperforms models of the same class such as the Semi‐ProtoPNet, Ps‐ProtoPNet, Gen‐ProtoPNet, NP‐ProtoPNet, and the standard ProtoPNet for the classification task.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.