Abstract

Exergy analysis is used as a tool to analyze the performance of a refrigeration system. In this paper, it is based on the following conditions: the solar radiation is set as 750 W/m2, the refrigerating capacity is 10 kW, R141b is fixed as the refrigerant in the refrigeration cycle and ambient temperature to be the reference temperature is 31°C. The exergy analysis results of the solar ejector refrigeration system shows that irreversible loss comes from all components and depends on the operating temperatures. The exergy efficiency increases with the condensation temperature’s decrease or the evaporation temperature’s increase. In the specific evaporation temperature and condensation temperature, the optimum generating temperature can be get when the system exergy efficiency is at its maximum. For the operating conditions in this paper, the optimum generating temperature is 95°C.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call