Abstract
In order to maintain a stable thermal environment of the data center, air-conditioning systems for the data center are in high energy consumption operation state yearly. Airflow organization in a data center impacts the cooling effectiveness of the air-conditioning systems significantly. This paper investigated a small-scale data center by combine of measurement and CFD simulation. To supply accurate boundary conditions, site measurement was conducted to validate the simulation results. In this paper, three optimization approaches of airflow organization were proposed and simulated by CFD software. The cooling performance of these approaches were compared by the temperature of 16 points on the same plane (Z=1.5m) in the room. The results indicated that cold aisle closure could eliminate by-pass airflow but also worsen thermal environment. Setting air return on both sides of hot aisle got most significant improvement in cooling performance. The temperature of hot points could be decreased by 0.5~5°C.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.