The ac choppers are usually used as voltage regulators and voltage sag compensators. However, the voltage compensation range is usually limited to %20 of the nominal voltage. Although the ac choppers can compensate deeper voltage sags from the structure point of view, it can be a challenging issue as it is not equipped with energy storage. To compensate deeper voltage sags with a series connected ac chopper it is necessary to boost more power from the faulted grid. This causes considerable increase in the grid current. Consequently, the grid current rating might be violated. Also, the additional voltage drop on the line impedance can be harmful for the adjacent loads. As a result, it seems that application of the series connected ac chopper to compensate voltage sags is really a challenging problem. This paper proposes new applications of the series connected ac chopper. The series connected ac chopper is used as overvoltage compensator and downstream fault current limiter (FCL). The proposed applications are demonstrated using simulation results in the PSCAD/EMTDC environment.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.