Abstract

This study assessed the performance of rainwater-harvesting systems installed for selected public utilities in the northern provinces of Vietnam where rainwater was collected, stored in stainless steel tanks, and treated with a complex filtration unit and Ultraviolet (UV) disinfection system (full system). Results from an operation of over 5years show that the untreated rainwater could not be used directly for drinking purposes as it was contaminated with bacteria (total coliforms TC = 200-300CFU/100ml, Pseudomonas aeruginosa PA = 40-160CFU/100ml), and turbidity = 2-4 NTU. Most of the heavy metals detected were found below the standard limits. Phenol and its derivatives were detected occasionally as higher than the standard value (1μg/L). After treatment, all parameters met the drinking water standards. The capital costs of the rainwater systems were approximately US$200/m3 and US$180/m3 for a full system and simplified system (without complex filtration unit), respectively, while the operation and maintenance (O&M) costs were 3 cents/L and 0.8 cents/L on average for a full system and simplified one, correspondingly.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.