Abstract

Off‐specification operation and downtime are important considerations in designing system reliability in ultraviolet (UV) light disinfection systems. This research analyzed the residual risk of Cryptosporidium infection from surface water supplies—after implementation of UV disinfection—and the corresponding UV disinfection system reliability requirements. The author concluded that achieving a maximum downtime of 0.01% (4.4 min/month) is unrealistic, even with standby power and an uninterruptible power supply. Furthermore, starting from 0.01% downtime, seemingly minor increases in downtime significantly reduce the net disinfection credit and result in diminishing returns, regardless of the validated UV disinfection system credit. Providing redundant equipment, standby power, active series compensators, and uninterruptible power supplies can increase UV disinfection system reliability. Judicious application of these and other mitigation measures will help maximize the effectiveness of UV disinfection for regulatory compliance.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.