Abstract

Maintaining a stable ice pad and indoor thermal environment satisfying requirements usually consumes high energy consumption in ice arenas. In this paper, a curling arena with ethylene tetra fluoro ethylene (ETFE) membrane structure is taken as an example to analyze the refrigeration load. Field tests for thermal environment are firstly carried out in this arena. Sources of refrigeration load are determined and possible reducing approaches are proposed to lower the energy consumption for ice making issue. It’s indicated that average refrigeration load of the curling ice is 152.8W/m2, among which long wave radiation contributes 55.5%. The ceiling temperature could reach as high as 26 °C, contributing more than 70% of the longwave radiation. It’s then noted that cavity ventilation could be a special method to lower the roof temperature on basis of avoiding condensation, reducing the refrigeration load by 7% for this special building with ETFE membrane envelope. It’s hoped that the current research will be beneficial for the design and operation of an ice competition circumstance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.