Abstract

The insulation capacity of electric power transformer will be affected by running in overheated conditions, and the winding hot spot temperature is the main limiting factor of transformer load, so the winding hot spot temperature should be measured accurately. Online temperature monitoring method using Fiber Bragg grating is presented in this paper. By the application of optical fiber grating temperature sensor in oil-immersed transformer, electromagnetic interference is avoided and direct temperature measurement of internal transformer can be realized. The system is built in an 110kV oil-immersed transformer and the transformer is put in operation for 10 months, it works safely and the measurement temperature data is stable and accurate. Based on the data, an accurate estimate of transformer life loss is work out through continuous integration of hot spot temperature and measurement time.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.