Abstract

Since natural gas is odorless, to assure the customer safety, odorants are added to it to alarm the consumer in the case of a gas leak. Although the odorization is a common practice in natural gas distribution systems, odor fading has been reported in pipelines, which is a great safety risk. This paper summarizes results of experiments conducted to investigate possible chemical and physical mechanisms responsible for odor fading. In these experiments, X-ray photoelectron spectroscopy (XPS) and gas chromatography were used to check the possible interactions of tertiary butyl mercaptan (TBM) as odorant with the pipe material. Evidences of chemisorption, adsorption and desorption of TBM on the iron oxide inside the pipe were observed. It was found that by increasing pressure, rusted surface of the pipe, and temperature or by decreasing the gas flow rate and odorant concentration the mercaptan removal was increased.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call