Abstract

This paper study the flow characteristic through a set of tube bank used as air preheater in a 100 MWe utility boiler. The study using numerical simulation commercial Computational Fluid Dynamic (CFD) software. A 3D model uses to analyze the flow characteristics with 3 load variations. The model using a steady-state flow assumption. The Steam Coil Air Preheater modelled as a porous medium (PM) to represent its effect on the airflow through it. Porous Medium model can avoid a time consuming mess generation and simulation. This paper using an empirical equation to define inertial resistance coefficient (C2). The model using Heat Exchanger Model, Energy Model, and Realizable k -Epsilon for turbulence viscous model. 100%, 75%, and 50% load variation simulated with the model. The simulation result in both quantitative and qualitative data. The velocity and pressure distribution affected by the load variation, geometrical shape change, and tube bank set. Some secondary flow observed due to geometrical change along with the flow. The heat transfer characteristics observed with temperature distribution show that it affected by the flow characteristic.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.