A finite element numerical model has been developed for the simulation of the ground heat exchangers (GHEs) in alternative operation modes over a short time period for ground-coupled heat pump applications. Comparisons between the numerical and analytical results show that the finite line-source model is not capable of modeling the GHEs within a few hours because of the line-source assumption. On the other hand, the experiments with respect to the alternative cooling and heating modes have been undertaken during a short-time period. The comparisons show a reasonable agreement between the numerical and the measured data. The results illustrate that the finite element numerical model can be used to simulate the heat transfer behavior of the GHEs in short time scales instead of the typical finite line-source model. Finally, the variation of the U-tube pipe wall temperatures demonstrates that the discontinuous operation mode and the alternative cooling/heating modes can effectively alleviate the heat buildup in the surrounding soil.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.