Abstract

Abstract An analytical and experimental investigation of air-cooled condensers for small-scale ammonia-water absorption heat pumps is presented. Conventional round-tube corrugated fin design and a novel multi-pass tube array design are considered for a condenser operating at severe ambient conditions within a compact footprint. Segmental heat and mass transfer models are developed to gain a deeper understanding of the characteristics of each design. Predicted heat duties are within 5% of the measured values. The limitations of correlations to predict air-side pressure drop in corrugated fins are identified. The performance of the novel multi-pass tube array condenser was comparable to that of conventional condensers, but is determined to be air-side limited throughout length of the heat exchanger. An improved multi-pass condenser design with fins for increased air-side area is proposed using the insights gained from the modeling and experiments. This design meets the heat duty requirements at severe ambient conditions, while decreasing the size of the heat exchanger by 33%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.