Abstract
It is very difficult to detect an islanding condition of a power distribution line with conventional voltage or frequency relays while the output power and the load power of utility interactive PV inverter units are in nearly balanced state in both active power and reactive power. This is because a sufficiently large voltage or frequency change cannot be expected at such a balanced state. Many studies have been reported so far to complement dead bands in combination of active and passive methods to prevent the islanding, but none of them has been successful. This paper presents the principle of a new active method called slip mode frequency shift (SMS). With this method the reactive power between the inverter and the load is made unbalanced intentionally to cause the frequency to shift as if it slips down a slide. The performance when the dead bands are eliminated effectively in the range of practical use has been examined through simulation and experiments.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.