Abstract
This paper proposes a novel hybrid approach for islanding detection of inverter-based distributed generations (DG) based on combination of the Slip mode frequency-shift (SMS) as an active and rate of change of frequency (ROCOF) relay and over/under frequency relay as passive methods. This approach is utilized to force the DG to lose its stable operation and drift the frequency out of the allowed range of the frequency threshold. Performance of the proposed approach is evaluated under the IEEE 1547, UL 1741 and multiple-DG operation. The simulation results demonstrate the effectiveness of the proposed approach for detection of islanding, especially for loads with high quality factor. It operates accurately under the condition of load switching and does not interfere with the power system operation during normal condition. In other words, not only it holds the benefits of both SMS and ROCOF, but also it removes their drawbacks by having less non-detection zone and faster response.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.