Abstract

To avoid the needless trip by magnetizing inrush current, the second harmonic component is commonly used for the blocking differential relay in power transformers. However, the second harmonic component in fault current is increased by the introduction of underground 500 kV lines. This paper describes a new method to discriminate internal fault from inrush current by the sum of active power flowing into transformers from each terminal. The average power is almost zero for energizing, but an internal fault consumes large power. To check the performance of this method, actual inrush current and voltage waveforms of a 500/154 kV transformer are accurately measured by digital equipment. The usefulness is confirmed by applying the method to the measured inrush and simulated fault data.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.