Abstract

A high-temperature superconducting (HTS) cable system with the 22.9 kV, 50 MVA, and 410 m length is installed and operated at 154 kV Icheon substation of Korea Electric Power Corporation (KEPCO). Unfortunately, it is a difficult task to diagnose and monitor electrical and thermal characteristics of the HTS cable system in a real-time manner. In order to protect operational failures of grid-connected HTS cable systems, this paper proposes time-frequency domain reflectometry (TFDR) and analysis techniques, i.e., time-frequency cross correlation and instantaneous frequency estimation. To verify the performance of the proposed method, the temperature is changed via the cryogenic refrigeration system and the status of the grid-connected HTS cable is monitored via TFDR in a real-time manner.