Abstract
High-voltage (HV) circuit-breakers (CBs) often consist of several making and breaking units (MBUs) in series. A multi-unit circuit-breaker EMTP® model is proposed to analyse the effects of non-simultaneity between MBUs of the same pole. The model allows for simulations of high-frequency voltage and current transients during opening or closing operations. The simulations include the non-simultaneity of MBUs of the same pole or differences in dielectric withstand characteristics for vacuum circuit-breakers (VCBs) and SF6 CBs. According to simulation results, the maximum non-simultaneity of MBUs of the same pole, as permitted per international standards, can lead to multiple re-ignitions during opening or excessive overvoltages during closing operations. These phenomena are rarely simulated with conventional CB models. The simulations also highlight the important challenges facing high-voltage VCB design due to the inherent characteristics of vacuum bottle technology. The proposed models serve as useful tools for understanding and studying the effect of multi-unit CBs in various system studies and advanced diagnostics.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.