Abstract

A basic CO2 transcritical/subcritical commercial refrigeration system is considered, applied to cold rooms and display cabinets in a supermarket. Subcooling of the refrigerant or heat recovery from condensation can be performed, taking advantage of a large fire prevention water tank. The whole refrigeration system is modelled in a TRNSYS environment, taking into account the hourly weather data and calculating the hourly cooling load demand from display cabinets and cold rooms equipment. New types have been written to describe display cabinets and cold rooms, CO2 refrigerating units and a particular water store.Simulations consider a simple double compression cycle with liquid receiver, and other options among which an auxiliary compressor. Results show that CO2 plants are feasible and energetically acceptable in mild climates, provided that improvements to standard cycle are adopted. Furthermore, heat recovery can be effectively performed through the employment of a heat storage.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.