Abstract
The erosion of the cohesive layers of particulate matter that causes discolouration in water distribution system mains has previously been modelled using the Prediction of Discolouration in Distribution Systems (PODDS) model. When first proposed, PODDS featured an unvalidated means by which material regeneration on pipe walls could be simulated. Field and laboratory studies of material regeneration have yielded data that suggest that the PODDS formulations incorrectly model these processes. A new model is proposed to overcome this shortcoming. It tracks the relative amount of discolouration material that is bound to the pipe wall over time at each of a number of shear strengths. The model formulations and a mass transport model have been encoded as software, which has been used to verify the model's constructs and undertake sensitivity analyses. The new formulations for regeneration are conceptually consistent with field and laboratory observed data and have potential value in the proactive management of water distribution systems, such as evaluating change in discolouration risk and planning timely interventions.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.