Abstract

In this paper a three-phase autotransformer is represented by inductance matrix for short-circuit studies. The inductance matrix consists of winding self-inductances and corresponding mutual inductances between windings. For single phase-to-ground fault the inductance matrix model results are compared to symmetrical components results, commonly used to analyze unsymmetrical faults in three-phase power systems. The influence of a delta connected tertiary winding on un-faulted phase voltages and asymmetrical fault current distribution is analyzed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.