Abstract

In order to improve the fault tolerance and solution efficiency of power grid fault diagnosis model, a distribution network cyber physical system (CPS) fault diagnosis model based on advanced digital power system simulator (ADPSS) and IEC61850 is proposed. Firstly, the action rules and action status of CPS fault mode of distribution network from the whole correlation of fault element, protection action and circuit breaker trip, and the CPS grid topology of distribution network is constructed in ADPSS based on the topology and component characteristics of system. Secondly, according to the IEC61850 unified information model and modeling rules for the protection function of system equipment and operation function of circuit breaker, an information model with alarm, measurement, protection and fault recording logic is established. Then, the action status is obtained and used for the establishment of the distribution network fault diagnosis model by parsing the GOOSE message. Finally, the proposed modeling method and fault diagnosis strategy is validated through the test case.