Abstract
<span>During energization of no – load transformers, a high and peaky current flow on the primary side which has rich second harmonics. This current is magnetising inrush current and it is generated when transformer core is driven deep into saturation. This current has various disturbances on transformer attribute; reduced life-span, major voltage drop, insulation weakening, electrical and mechanical vibrations in coils, difficulties in protecting relays and all leads to poor power quality of the electric system. This paper presents the analysis and comparison of recent techniques to reduce the magnitude of inrush current during energization of power transformer. The simulation results are provided for Pre – insertion of resistors, Controlled swithing and Pre – fluxing method. The best method is suggested for mitigating inrush current by simulating in MATLAB/SIMULINK environment.</span>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Indonesian Journal of Electrical Engineering and Computer Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.