Abstract

ASDEX Upgrade (AUG), an experimental tokamak for nuclear fusion research, requires an electrical power up to a few hundred MVA for a time period of 10-20 s. The power and energy is provided by isolated networks based on flywheel generators. About twenty power transformers must be energized on a daily basis to get the pulsed power supply operational for plasma experiments. Nuisance interactions of transformer inrush currents with the protection system of the synchronous machines and capacitor banks used for reactive power compensation must be avoided. To investigate the effects of inrush transients in present and future configurations, measurements were performed and a simulation model based on an equivalent magnetic circuit representation of the transformer was derived. The paper describes the model, results of simulation and measurement and shows which measures were taken to keep transients in the isolated network at an acceptable level.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.