Abstract

This paper presents a novel approach for minimizing magnetic inrush current to a level as low as no load current during controlled energization of coupled un-loaded power transformers in presence of residual fluxes without employing load side voltage measurements. The suggested method has been evaluated for power transformers having various winding connections, design configurations (magnetically dependent and independent type), its side of energization (Δ or Y) and different level & polarities of residual fluxes. The effect of breaker performance in terms of variation in dielectric properties and operating time of circuit breakers has also been explored. The method is applied successfully on various 765/400/33 kV power (auto) transformers with delta connected tertiary winding on an existing Indian power transmission network and results, for a couple of cases, are presented. Based on simulation results, it has been observed that the inrush current for a number of transformers has been managed below 5% of its full load current rating. This validates applicability of the proposed technique in real system applications.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.