Abstract

This paper describes an asymmetric control method for the firing angle and a start/stop timing shift control of four thyristor converters called “Booster PS" to minimize the reactive power fluctuation during plasma initiation in JT-60SA. From the simulation using the “PSCAD/EMTDC" code, it is found that these control methods can drastically reduce the reactive power induced by the four units of the “Booster PS". In addition, the voltage fluctuation of the motor-generator connected to the “Booster PS" is expected to be suppressed. This can also contribute to achieve stable control of the JT-60SA magnet power supplies.