Abstract

To investigate the behavior of metallic particles in 3-phase gas insulated buses (3-phase GIB), we conducted a test by using a 3-phase 275kV, ac, 60Hz full-scale model. The test results revealed that in a 3-phase electric field, unlike in a single-phase field, metallic particles were trapped on and around the high-voltage conductors and revolved circumferentially. Computer analysis shows that it was closely related to locational and periodic changes in the electric field provided by the 3-phase GIB, and that there were points on the high-voltage conductors in which metallic particles were readily trapped. It also was proved that phenomena peculiar to the 3-phase GIB could be reproduced very well by computer simulation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.