Abstract

The paper investigated the behavior and partial discharge (PD) characteristics of a metallic particle under residual dc voltage, using the setting conditions and length of the particle, the applied dc voltage, and other factors as parameters and a gas insulated switchgear (GIS) bus bar model equivalent to that of an actual 300 kV GIS. A metallic particle repeated reciprocating movement at a relatively high frequency of about 5 times per second between the high-voltage conductor and the sheath when the electric field at the bottom surface of the tank exceeded its lift-off electric field. It emerged that, in the process of this reciprocating movement, PD occurred at the moment when the particle collided with the high-voltage conductor. In addition, when a particle collided with the electrode, the electrical charges moved and the residual dc voltage was damped. Conversely, where the sheath side was insulation-coated, the particle did not move at the normal operating voltage level, and even though it moved if vibration was applied, its movement stopped relatively soon. If a metallic particle exists in GIS and moves, there is concern that the insulating performance may decline significantly. When a metallic particle moves under dc voltage, a relatively stable PD is generated and consequently, for example, the PD measurement is considered an effective way to detect a particle. It is also considered effective to take physical measures, such as using an insulating sheath at the bottom surface of the tank to restrain the behavior of particles.