Abstract
The experimental conductive heat transfer results for flow through inserted perforated twisted tapes in a horizontal tube during condensation of pure R-245fa vapor. The test section consisting of two separate coaxial double pipes assembled in series, acted like a counter flow heat exchanger, where the refrigerant condensed inside the inner tube by rejecting heat to the cooling water flowing inside the outer tube in reversed direction. Data for three perforated twisted tapes having constant twist ratio of 7.1 mm and pitch of perforation as 12.5, 25.0 and 37.5 mm, inserted one by one in full length of test condenser by varying refrigerant mass flux from 100 to 200 kg/m2 s in steps of 50 kg/m2 s for the range of vapor quality from 0.1 to 0.9, were collected together with flow and without insert (plain tube). It has been found that the perforated twisted tape insert having pitch of perforation equal to in order of 12.5 mm gives the highest value of average heat transfer coefficient and is of the order of 37.5 % more than that of the plain one and the correlation predicts the experimental data within an error band of ±15 %.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.