Abstract
Modeling of three-phase transformers with three-limb cores is important. Such units are very ubiquitous and are asymmetric due to the different lengths of the three limbs of the core. It is, therefore, important to devise a measuring procedure where the (λ-i) characteristics of the three limbs and the zero-sequence (λ <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">0</sub> -i <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">o</sub> ) characteristic due to the tank can be determined. A simulation program is developed so that currents at no-load and symmetric or asymmetric loads can be computed. Measured currents are compared with computed results for 2.3 kVA and 45 kVA units.